Control Concepts IslaGuard IL277Y100
Surge Protector; 100000 A (Phase); 277/480 VAC; 47 to 63 Hz; Voltage and Phase
Operating Voltage Range +/– 15%
Fault Current Rating (AIC) 14 kAIC
Operating Frequency Range 47–63 Hz
Capacity Continuous
50 Ω EMI/RFI Attenuation 40 dB
Dry Contact Rating 125 VAC, 8A, 1.0 pf
Response Time < 0.5 ns
Operating Temperature –40°C to +50°C
Operating Humidity 0% to 95%
Certifications UL 1449, CUL, CE
Clamping
UL 1449 Classification*
120/208
Line to Neutral 400 Volts
Line to Line 800 Volts
Line to Ground 400 Volts
Neutral to Ground 400 Volts
120/240
Line to Neutral 400 Volts
Line to Line 800 Volts
Line to Ground 400 Volts
Neutral to Ground 400 Volts
277/480
Line to Neutral 800 Volts
Line to Line 1,500 Volts
Line to Ground 800 Volts
Neutral to Ground 800 Volts
480
Line to Line 1,500 Volts
Line to Ground 1,500 Volts
* UL classifications for other voltages available upon request.